Quality is not negotiable. Every transformer, reactor, and choke that leaves our facility is tested through a complete 10-test battery. A full test report with measured values is included with every unit.
Verifies turn ratio and output voltage accuracy under no-load conditions.
THRESHOLD
Output voltage within ±2% of specification
Measures winding impedance and copper loss under short circuit conditions.
THRESHOLD
Impedance measured and recorded for reference
Measures core magnetising current to verify core quality and winding integrity.
THRESHOLD
No-load current within design limits
Continuous no-load operation for 10 hours with temperature measurement.
THRESHOLD
50°C to 55°C temperature rise above ambient
Continuous full load operation for 10 hours with temperature measurement.
THRESHOLD
80°C to 90°C temperature rise above ambient
Applied voltage test between primary, secondary, and frame to verify insulation integrity.
THRESHOLD
2KV-5KV applied for 1 minute, no breakdown
DC insulation resistance measurement between all windings and frame.
THRESHOLD
Minimum 1000 MΩ at 2500V DC
Verification of conductor wire insulation integrity.
THRESHOLD
Conductor insulation meets Class F specification
Confirmation that conductor insulation is rated for Class F operation (160°C).
THRESHOLD
Class F insulation verified
Core material verification and no-load watt loss measurement.
THRESHOLD
50-500 Grade CRGO/CRNO, 1-4.5 W/kg watt loss
| HIGH VOLTAGE TEST | 2KV-5KV |
| MEGGER TEST | 1000 MΩ / 2500V |
| NO-LOAD TEMP (10 HRS) | 50°C TO 55°C |
| LOAD TEMP (10 HRS) | 80°C TO 90°C |
| CONDUCTOR INSULATION | 160°C |
| INSULATION CLASS | CLASS F |
| CORE GRADE | 50-500 Grade |
| CORE WATT LOSS | 1-4.5 W/kg |
Every transformer undergoes the full 10-test battery immediately after fabrication and assembly. The no-load and full load temperature tests each run for a continuous 10-hour cycle with periodic temperature measurements recorded. Units that do not meet all test thresholds are rewound or rebuilt before retesting.
The complete test report — including all measured values, test date, technician signature, and unit serial number — is printed and included with the transformer at dispatch. This report serves as your permanent quality record and is required for warranty claims.
We also maintain internal test records for every unit built, indexed by serial number. If you need a duplicate test report or have questions about a unit's test results, contact us with the serial number and we will retrieve the original test data.
Every unit we build passes the full 10-test battery before it ships. Send us your specifications and we will build it right.